P4204CF Power Supply / Relay Output Module

P4204CF Power Supply / Relay Output Module

The P4204CF is designed to meet the requirements of UL864 for UL listed commercial fire systems. Note : the P4204CF is not required in Canada. Use the P4204 in Canada.

The P4204CF is a dual purpose power supply/output module, providing programmable relay outputs for controlling external devices and power to repower the Combus... to provide additional power as required for downstream devices which are powered off of the Combus:

Supplied in a panel enclosure, the P4204CF contains a standard P4204 module, a 350mA battery charger and a 16VAC 40VA transformer, with remaining space for two 7Ah batteries and one P4108A hardwired zone expansion module.

Note :

to comply with UL requirements, the rated capacity of the PC4204CF for repowering the Combus is reduced to 550mA.

P4204CF Panel


  • 4 fully programmable high current Form'C' relays with contacts rated at 2 A @ 30VDC

  • provides 550mA @ 12VDC to power direct connected devices or repower the Combus (based on 24 hour standby with two 7Ah batteries) (uses relay #1 when repowering Combus)

  • complete with supervised battery charger : 12VDC, 350mA charging current for sealed lead-acid rechargeable batteries

  • connect up to 16 modules per system for 64 relays total

  • each relay programmable to activate for any of 59 options

  • fully supervised for low battery, and aux supply and AC power loss

  • connection for external tamper… supervised by system

  • connect up to 1,000' (305m) from control panel via COMBUS

  • operating environment
    - 32 to 122°F (0 to 50°C)
    - 90% RH non-condensing

  • current draw …30mA (from Combus)

  • dimensions
    12"H x 12"W x 4.5"D
    (30.5 x 30.5 x 11.5cm)

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

Partner Premier SeriesRepowering the Combus

 

Up to 16 P4204CF modules may be installed in the Combus wherever additional power is required downstream of the P4204CF for additional modules and devices powered off of the Combus.

 

Repowering the COMBUS

Partner Premier SeriesTypical System Arrangement

Typical System Arrangement

Partner Premier SeriesOrdering Information

  P4204CF ....

  power supply/ relay output module with 4 relay outputs for fire installations requiring UL864 listing includes:

- P4052CR red cabinet, 12"H x 12"W x 4.5"D (30.5 x 30.5 x 11.5 cm)

- P4204 module

- PT1016 transformer, 16 VAC, 40VA

- space for two 7Ah, 12volt lead-acid batteries

- space for one P4108A hardwire zone expansion module

Partner Premier SeriesListings

USA

UL864

...Control Units System
...(L, CS, -A, M, SS, WF)*

UL1610

...Central Station Burglar Alarm

UL609

...Local Burglar Alarm

UL365

...Police Station Burglar Alarm

UL985

...Household Fire Warning

UL1023

...Household Burglar Alarm

CANADA

ULC-S527

...Central Station Fire Alarm

ULC-S302

...Central & Monitoring Station
...Burglar Alarm

ULC-S303

...Local Alarm
...(Commercial Burglary)

ULC-S310

...Household Burglar Alarm

ULC-S545

...Household Fire Warning

UL294

...Access Control

Partner Products

Back to Products List

Top of Page