The P-16-128CF is the UL listed commercial fire version of the P-16-128
security control panel. As such, the P-16-128CF has the same system
expandability and features as the P-16-128 plus added features and
expandability for commercial fire applications as described herein.
|
 
|
|
|
In addition to all of the features of the P-16-128 (see separate spec sheet),
the following are additional hardware and software features of the
P-16-128CF for use in commercial fire applications :
- P-16-128CF control panel is supplied in red system cabinet c/w :
|
| - |
P4701 fire module |
|
| - |
16VAC, 40VA transformer |
|
- PC4701 fire module includes :
|
| - |
1 Class 'B' / Style 'B' two-wire smoke detector zone accommodating
30 12VDC compatible detectors |
|
| - |
1 Class 'B' / Style 'B' waterflow zone |
|
| - |
two supervised communicator outputs |
|
| - |
terminal connection for house telephone |
|
| - |
1 fire alarm actuated relay… Form'C', rated 2 A, 30VDC |
|
| - |
1 fire trouble actuated relay… Form 'C', rated 2 A, 30VDC |
|
- up to 112 PARTNER-AMS-220 addressable smoke detectors can be added
to the system spread over one or both of the addressable loops :
|
| - |
addressable fire zones may be programmed as the following types |
|
| - |
standard fire zones |
|
| - |
auto-verify fire zones |
|
| - |
delayed fire zones (for residential only) |
|
- all hardwired zones on the P-16-128CF can be programmed as fire
zones with the following zone types :
|
| - |
standard fire zones |
|
| - |
waterflow zones |
|
| - |
auto-verify fire zones |
|
| - |
delayed fire zones (for residential only) |
|
| - |
fire supervisory zones |
|
- programmable fire alarm output patterns… steady, temporal pattern,
CA pattern, pulsed, or strobe fire.
- programmable fire bell options… bell cut-off time and fire silence
inhibit time.
- all P4702BP bell outputs are supervised for :
|
| - |
short circuit |
|
| - |
open circuit |
|
| - |
ground fault |
|
- alarm autoscroll… displays fire alarms and selected trouble
conditions at 2 second intervals on system LCD keypads.
Items displayed include :
|
| - |
first fire alarm [zone label] |
|
| - |
fire alarm [zone label] |
|
| - |
fire supervisory [zone label] |
|
| - |
fire bell has been silenced |
|
| - |
bell zone trouble |
|
| - |
failure to communicate |
|
|
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
|
|
|

|
|
- fire drill… activates main bell output and P4702BP fire bell outputs
according to their programmed fire signalling modes without activating
other functions and without sending reporting codes to the central
station. Keypads display "Fire Drill in Progress" during test. If an actual
alarm occurs during test, the test is automatically cancelled and the
standard fire alarm functions occur.
- fire inspector test… ensures that all fire initiating devices are communicating
and are supervised. All test results are logged to the system
event buffer.
- scheduled smoke detector tests… 50 time/ date smoke detector test
schedules programmable by partition… for addressable detectors only
- lamp test… use keypad to activate annunciator lights for 2 seconds
|
|
 
|
|
In addition to all of the modules available for the P-16-128 (see separate
spec sheet), the following are specially designed for use with the
P-16-128CF in commercial fire applications :
- P4702BP fire system bell panel… provides 2 supervised
Class'B' / Style'Y' bell outputs c/w battery charger, 28 VAC 170VA
transformer, and cabinet with space for two 12 volt 4 Ah sealed
lead-acid rechargeable batteries.
- P-16-128CF fire system quad relay / power supply module…
similar to P4204, but c/w battery charger, 16 VAC 40VA transformer,
and cabinet with space for two 12volt 7 Ah sealed lead-acid
rechargeable batteries.
- P4612 fire zone annunciator (1) … 12 zone, surface mount, keypad
style, plastic annunciator. Includes common fire zone trouble, fire bell
zone trouble, common system trouble, and AC 'on' indicators.
|
|
(1) |
system can also include P4632 and P4664 thirty two and
sixty four zone point / graphic annunciators to annunciate fire zones,
security zones, and common system indications. |
|
- P4350R fire system external battery charger… for longer standby
time required by listed fire systems.
- keypads with red bezels for fire application… at least one PRS 400F
must be used with the P-16-128CF
|
| - |
keypad piezo buzzer will sound continuously if communication is
lost with control panel |
|
| - |
PRS 400F… same as PRS 400 but with red bezel. Five function
keys have fire system specific assignments : |
|
| |
- Silence Trouble |
|
| |
- Silence Bells |
|
| |
- Fire Reset |
|
| |
- Fire Drill |
|
| |
- Lamp Test |
|
|